InstallatIon
11.2 Compatible 2-Wire Smoke Detector Chart
Manufacturer Model Detector
ID
Base Base
ID
DC
Voltage
Range
# of
Detectors
(12V/24V)
Zone
Expansion
Modules
Panel
Zones
Hochiki
SLR-835B-2
SLR-835BH-2
HD-6 N/A 8-35 14
715, 715-8,
715-16
9 & 10
EST
521B, 521BXT,
521NB, 521NBXT
S09A 6.5-20 12
715, 715-8,
715-16
9 & 10
System Sensor 2W-B, 2WT-B A 8.5-35 10
715, 715-8,
715-16
9 & 10
System Sensor 2WTA-B A (*) 8.5-35 12
715, 715-8,
715-16
9 & 10
System Sensor 2WTR-B A (*) 8.5-35 1
715, 715-8,
715-16
9 & 10
System Sensor 1151, 2151 A B110PL, B401 8.5-35 10
715, 715-8,
715-16
9 & 10
(*) = Must be used in conjunction with System Sensor Polarity Reversal Module model RRS-M0D. See 1.19 for Installation Diagram
Figure 6: Compatible 2-Wire Smoke Detectors