1912XR Installation Guide
Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 11
7.7 Battery supervision
The 1912XR tests the battery once every hour when AC power is present. The test is done at 15 minutes
past the hour and lasts for five seconds. A load is placed on the battery and if its voltage falls below
11.9 VDC, a low battery is detected. If AC power has failed, a low battery is detected any time the battery
voltage falls below 11.9 VDC.
If a low battery is detected with AC power present, the test is repeated every two minutes until the battery
charges above 12.6 VDC; the battery restored voltage. If a faulty battery is replaced with a fully charged
battery, the restored battery will not be detected until the next two minute test is done.
7.8 Battery cutoff
The panel disconnects the battery any time the voltage of the battery drops below 10.2 VDC. This prevents
deep discharge damage to the battery.
Bell Output
8.1 Terminals 5 and 6
Nominal 12 VDC is supplied by terminal 5 on the panel to power alarm bells or horns. The output is rated
for a maximum output of 1 Amp. This output can be steady or pulsed depending upon the Bell Action
specified in Output Options. Terminal 6 is the ground reference for the bell circuit.
Keypad Data Bus
9.1 Description
Terminals 7, 8, 9, and 10 of the 1912XR panel are designated as the keypad data bus. You can connect
any combination of Security Command keypads and loop expanders up to the maximum of eight devices.
9.2 Terminal 7 - RED
This is a positive 12 VDC for powering Security Command keypads and loop expanders on the keypad
data bus. This is also where power for any auxiliary device is supplied. The ground reference for terminal 7
is terminal 10. The maximum output is rated at 600mA when using a 40VA transformer. The output current
is shared with the smoke detector output on terminal 11 and Loop 5. The auxiliary output power can also
be internally connected to the common terminal of relay output 1 by installing the J15 jumper. All auxiliary
devices totalled together must not exceed the panel's maximum current rating.
Terminals 7 also provides power for devices used on 862N, 862P, 872, and 881 expansion cards.
9.3 Terminal 8 - YELLOW
Data receive from keypads and loop expanders. It cannot be used for any other purpose.
9.4 Terminal 9 - GREEN
Data transmit to keypads and loop expanders. It cannot be used for any other purpose.
9.5 Terminal 10 - BLACK
Terminal 10 is the ground reference for Security Command keypads, loop expanders, and any auxiliary
devices being powered by terminals 7 or 11.
Smoke and Glassbreak Detector Output
10.1 Terminal 11
This is a positive 12 VDC for powering 4-wire smoke detectors or other powered devices. This output can
be turned off by the user for 5 seconds using the Sensor Reset Menu Option to reset latched devices.
Terminal 10 is the ground reference for terminal 11.
10.2 Current rating
The Output current from terminal 11 is shared with terminal 7 and terminal 12. The total current draw of all
devices powered from the panel must be included with terminal 7 calculations and must not exceed the
maximum output rating of 600mA.