Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 22
1912XR Installation Guide
26.1 Indicating circuit module installation
AC BELL
AC
1
2
34 56 7 89
10
11
12
13
14 15
16
17 18 19
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
GND
RED YEL GRN BLKB + B - SMK L5+ L5- L1 L2 L3 L4GNDGND
AUXILIARY
POWER
SUPPLY
24 VDC 5 Amp
Maximum
Power Supply
Trouble Contacts
N/C
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
Indicating Circuit Module
DMP Model 866
37mA at 12 VDC
The Auxiliary Power Supply and Indicating
Circuit Module trouble contact Loop must
be programmed as a Supervisory Type Loop
and must be selected for display in the
keypad status list.
See section 10.6 in the 1912XR
Programming Manual (LT-0171).
1k
3.3k Resistor
DMP Model 309
1k
1k
NOTE: If an auxiliary supply is not used,
terminals 3 and 4 on the 866 Indicating
Circuit Module can be jumpered together
to supply bell power from the 1912XR panel.
A maximum of 1 Amp at 12 VDC is available
from terminal 5 of the 1912XR.
Auxiliary power supply must be regulated
UL listed for Fire Protection Signaling
Service.
Power supplies must have battery backup.
J4
Dual Line Expansion
J10
Battery Only Restart
J16
Command Processor Reset
1k
EPROM Socket
Each 866 Indicating Circuit
Module in alarm draws up to
35mA from its terminal 3 alarm
input.