Internet.
on XRSuper6 and XR20, and up to eight keypads on the XR40. Model 690/690F, 790/790F,
10.
* These devices have not been investigated by a Nationally Recognized Testing Laboratory (NRTL).
J4
RED
PROG
J8
XRSuper6/XR20/XR40
Command
Processor™ Panel
J16
Command
Processor Reset
J7
RJ SUP
AC
1
2
3
4567
8
10
11 12 13 14
15
16 17 18
19
9
20
21
22 23
24
25 26
+B
BELL
GND
SMK
RED
YEL
GRN
BLK
Z1
Z2 Z3 Z4
Z5
Z6
Z7
Z8 Z9
Z10-
AC
-B
GND
GND
GND
GND
Z10+
ProgrammerHeaderJ8
Use DMP Model 330 Harness
RJ Cable Monitor
J7. Use DMP Model
306 Harness
Phone Jack Connector
16 to 18
gaugewire
Maximum AC
Wire distance –
16gaugewire:70feet
18gaugewire:40feet
RED
BLACK
Cold Water Pipe
Earth Ground
s
s
s
s
ACWiringmustbeinconduitandexitout
the left side of the enclosure.
Wiringonterminals5through26mustexit
rightandmaintaina1/4"separationfrom
theACandbatterypositivewiring.
USE MARKING
HouseholdFireandBurglaryWarningSystem
Control Unit.
CommercialBurglarandHoldupAlarmSystem
Control Unit.
NFPA 72
This equipment should be installed in accordance with Chapter 2
of the National Fire Alarm Code, ANSI/NFPA72-1996,(National
Fire Protection Association, Batterymarch Park, Quincy, MA
02269).Printedinformationdescribingproperinstallation,
operation,testing,maintenance,evacuationplanning,andrepair
service is to be provided with this equipment. Warning:Owner’s
instruction notice, not to be removed by anyone except occupant.
HOUSEHOLD FIRE WIRING
Recognizedlimitedenergycablemustbe
usedforconnectionofallinitiating,
indicating,andsupplementarydevices.
POWER LIMITED
All panel circuits comply with the
requirements for inherent power limitation
and are Class 2.
AUX — Up to 500mA auxiliary current
at 10.4 to 13.2 VDC from Terminal 7.
TYPES OF SERVICE
Whenusedwiththe350AorEnclosure:
Suitable for Local and Police Connect
Mercantile Premises with Standard Line
Security, Local and Police Connect
Mercantile
Safe and Vault with Standard Line
Security,
DACT Central Station and proprietary.
Suitable for Household Fire and
HouseholdBurglary. Test weekly.
Suitable for Standard Line
Network Security.
SIA CP-01-2000 minimum system is
XRSuper6, XR20, XR40
UL listed local Bell,
and off premise DACT
communication to an
SCS-1R receiver plus
ANSI/SIA CP-01-2000
classifiedcompatible
DMP keypads as
indicated in the
installationguide.
Listed Resistors
1.0k Ohm -
DMP Model 311
3.3k Ohm -
DMP Model 309
Pluginto
120 VAC
60 Hz
outlet not
controlled
by switch.
J11
U11
EPROM
Socket
1
2
3
4
Zone 10 compatibility
identifier:A
Maximum operating
range:
8.8 VDC - 14.2 VDC.
See the panel
Installation Guide
(LT-0624)foralist
of approved 2-wire
smoke detectors.
DMP Transformers
Model 320 – 16.5 VAC 40 VA
Class 2 wire-in.
Model 321 – 16.5 VAC 40 VA
Class2plug-in.
Smoke Output: — 100mA at
10.4 to 13.2 VDC Terminal 11.
Verification
Zone
10
Control Unit
Delay
13.6 sec.
Smoke
Model
______
Detector
Delay
____sec.
Heat detectors, manual pull stations, or any other
shortingdevice.Unlimitednumberofunits.
Bell — 10.4 - 13.2 VDC
Totalcurrent:1.5Ampsmax.w/40VA
1K Ohm EOL
on each zone
3.3K Ohm EOLSwitched
Voltage
Output
Zone 10Keypad
Bus
SmokeZones 1 to 9 (1-5 on XRSuper6)Bell
Household System
Analarmsoundingdevicemust
be installed indoors so that it is
clearlyheardinallsleepingareas.
Secondary Power Supply
1.2Ampsmaximumchargingcurrent.Useonly
12VDCrechargeablebatteries.DMPModel367.
Replace every 3 to 5 years.
Minimumvoltageon
Auxiliary output to
process Sensor trips
is 10.2 VDC.
Terminals 5-20 are Power Limited.
ForWirelessDevices,ControlUnitdelayis0(zero).