XT Series Programming Guide Digital Monitoring Products
23
OUTPUT OPTIONS
Output Options
11.1 Output Options
This section allows you to program panel output options. Switched Ground (open
collector) outputs are available using the 4-wire output harness on the XT30/XT50
board. Wireless outputs are available when using the built-in 1100 Series Receiver of the
XT50 or an 1100D Series Wireless Receiver. Refer to the XT Series Installation Guide
(LT-0980) for complete information.
Select from the following output numbers:
• 1 to 4
• 31 to 34
• 41 to 44
• F1 to F20 (To Activate Z-Wave Favorites)
11.2 Cutoff Outputs
This option allows you to dene the operation of the four on-board annunciator outputs.
For each programming option, enter the number of the output you wish to activate or 0
(zero) for no output. Any or all of the available outputs can be programmed here to turn
off after the time specied in Output Cutoff Time. See the Output Cutoff Time section
for additional information. To disable this option, press any Select key to clear the
display of output numbers and then press COMMAND.
Note: Whenever an output is assigned in Output Options, that output cannot be turned
on from the User Menu.
11.2.1 Output Cutoff Time
If a Cutoff Output is assigned, you can enter a Cutoff Time for the output to remain
on up to 15 minutes. If the output is turned off manually, the cut off time is reset. The
Cutoff Time can be 1 - 15 minutes. Enter 0 (zero) to provide continuous output.
Note: The output is cutoff within 60 seconds of the programmed cutoff time.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not
reset. Both outputs turn off when the original time expires.
11.3 Communication Failure Output
This output/Favorite turns on when the panel fails to communicate with the receiver
after three successive dial attempts. Enter 0 (zero) to disable this output.
Note: To turn off the Communication Failure Output, disarm the panel or turn the
output off using the User Menu Outputs On/Off function.
11.4 Fire Alarm Output
This output/Favorite turns on any time a re type zone is placed in alarm. The output
turns off using the Sensor Reset option when no additional re type zones are in alarm.
Enter 0 (zero) to disable this output.
11.5 Fire Trouble Output
This output/Favorite turns on any time a re type zone is placed in trouble or when a
supervisory type zone is placed in alarm or trouble. The output turns off when all re
and supervisory type zones restore to normal. Enter 0 (zero) to disable.
11.6 Panic Alarm Output
This output/Favorite turns on any time a Panic Zone (PN) is placed in alarm. The output
turns off using the Sensor Reset option once all Panic Zones are restored. Enter 0 (zero)
to disable this output.
If a wireless output is programmed, the panel sends the Panic Test Cadence or the Panic
Alarm Cadence to the output when a Panic Test is performed or a Panic Zone is placed in
alarm.
11.7 Ambush Output
This output/Favorite turns on any time an Ambush code is entered at a keypad. The
output turns off using the Sensor Reset option. Enter 0 (zero) to disable this output.
11.8 Entry Output
This output/Favorite turns on at the start of the entry delay time. The output turns off
when the area disarms or the entry delay time expires. Enter 0 (zero) to disable.
OUTPUT OPTIONS
CO OUTS: - - - -
CUTOFF TIME: 0
COM FAIL OUT: 0
FIRE ALR OUT: 0
FIRE TRB OUT: 0
PANC ALM OUT: 0
AMBUSH OUT: 0
ENTRY OUT: 0