ZONE INFORMATION
If you select Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 as the Zone Type, the
zone must be assigned to an area. If you select Fire, Panic, Emergency, or Supervisory as
the Zone Type, these are 24-hour zones that are always armed and no area assignment is
needed. Press COMMAND to continue.
Caution: When a sensor reset is performed at the keypad, power will drop to devices
connected to zone 10 causing the panel to sense an open condition on all zone types
other than Fire (FI), Fire Verify (FV), and Supervisory (SV). Whenever non-Fire and non-
Supervisory zone types are used on zone 10, make the appropriate adjustments to the
zone Armed Action to prevent false alarms from occurring.
Refer to the Appendix for zone type specications and descriptions.
Note: For listed installations using wireless zones, do not use the FV zone type.
14.6 Area Assignment
For Area systems, enter the area number from 1 to 6 where this zone is being assigned.
For All/Perimeter systems, choose INTERIOR or PERIMETER.
For Home/Away systems, choose INTERIOR, PERIMETER, or BEDROOMS
• INT (Interior) - Assigns the zone to area 2, Interior.
• BDRM (Bedroom)- Assigns the zone to area 3, Bedrooms. This option is only
displayed in Home/Away systems.
• PERIM (Perimeter) - Assigns the zone to area 1, Perimeter.
14.7 Arming Zone Assignment
For Area systems, this option species the areas to be armed by the Arming Type zone.
Press the appropriate number keys on the keypad to assign areas 1 to 6. When disarmed,
all programmed areas are disarmed.
For All/Perimeter systems, choose PERIM or ALL. For Home/Away systems, choose HOME,
SLEEP, or AWAY.
Perimeter/All - Specify whether the arming zone arms just the Perimeter (PERIM) or the
Perimeter and Interior areas (ALL) for All/Perimeter systems. When disarming, all areas
are disarmed.
HOME/SLEEP/AWAY - Specify whether the arming zone arms the Perimeter (HOME), the
Perimeter and Interior (SLEEP), or all three areas (AWAY). When disarming, all areas are
disarmed.
Arming zone operation
If a bad (faulted) Priority zone is in the area being armed by an Arming zone, the arming
is stopped. If there are no Priority zones, or they are all in a normal condition, the
following applies:
When a non-Priority zone is bad when an area is armed with a keyswitch on an Arming
zone, the arming is delayed for ve seconds. If, during the ve-second delay, the
keyswitch is turned to disarm, the arming stops. If the keyswitch is held in the arming
position for the full ve seconds, the bad zone is force armed and the area is armed.
The ability to stop the arming does not apply if a wireless arming device is being used.
Refer to the Appendix.
Note: Arming from a zone, voice module, touch tone telephone, or Remote Link is not
affected by this operation.
14.7.1 Style
This option species the style for the arming/disarming operation. The default for
STYLE: is TGL (toggle). Pressing any Select key displays the STYLE options. To view more
style options press the command key. The following is a description of the action for
each option condition.
AREA NO: -
AREA: PERIMETER
INT BEDRM PERIM
AREA:
ARM AREA: PERIM
PERIM ALL
HOME SLEEP AWAY
STYLE: TOGGLE