3.7 EVENT MANAGER
This option specifies when non-alarm reports are sent to the receiver. This selection
does not affect zone alarm, zone trouble, zone restoral, supervisory, or serviceman
messages. Closing reports are not delayed if you have programmed a YES for the
Bell Test option.
SND - All reports are sent to the receiver as they occur.
DLY - All non-alarm reports are held until the panel's memory buffer contains 40
events on the XRSuper6, 66 events on the XR20, and 100 events on the XR40, or until
the panel's next communication with the receiver.
Note: If BELL TEST is YES, Closing reports are not delayed.
KEEP - All non-alarm reports are held in the panel's memory buffer until they are
overwritten by new activity. You can view the contents of the buffer using the DMP
Remote Link™ software, or the Display Events function in the User Menu. Contact ID,
Modem IIe, and 4-2 formats do not delay reports but send them as they occur.
Time update from the SCS-1 Receiver: The XRSuper6/XR20/XR40 requests a time
update each time (once each day maximum) the panel contacts the receiver. The
SCS-1 Receiver must have firmware version SCS/805 or higher and the Update Time
to Panel option must be set to YES in the receiver's Host Configuration screen. In
addition, the central station automation system must be configured to update the
time in the receiver at least once each day.
3.8 TEST FREQUENCY
Allows you to set how often the panel's test report is sent to the receiver. Enter
from 1 to 60 days. Enter zero to disable the test report.
3.9 TEST TIME
Press COMMAND to enter the Test Time. Enter the time of day the panel sends the
test report to the SCS-1 Receiver. Use entries between 12:00 to 11:59 and then
choose AM or PM.
3.10 RECEIVER 1 PROGRAMMING
Allows you to set the options for the first receiver the XRSuper6/XR20/XR40 panel
attempts to contact when sending reports. The XRSuper6/XR20/XR40 supports
communication to two receivers.
3.11 ALARM REPORTS
YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced, Ambush, Exit Error,
and System Recently Armed reports to be sent to this receiver.
3.12 SUPERVISORY/TROUBLE REPORTS
YES enables Supervisory, Trouble, Trouble Restoral, Force Armed, and Fault reports
to be sent to this receiver.
3.13 OPENING/CLOSING AND USER REPORTS
YES enables Opening/Closing, Door Access, Schedule and Code Changes, Bypass, and
Sensor Reset reports by user to be sent to this receiver.
3.14 TEST REPORT
Enter YES to enable the Recall Test report to be sent to this receiver.
3.15 BACKUP REPORTING
YES enables this receiver to be a backup to the other receiver in the event the other
receiver cannot be contacted.
Note: When Backup Reporting is set to YES, the Cellular Backup Output programmed
in Output Options is automatically set to zero.
BACKUP NO
O/C USER YES
SPV/TRBL YES
ALARM YES
TEST TIME
0 : 0 0 A M P M
RECEIVER 1 PROG
TEST RPT YES
TEST FREQ: 0
EVENT MGR: SEND
SND DLY KEEP
COMMUNICATION