20
XRSuper6/XR20/XR40 Programming Guide
Digital Monitoring Products www.dmpnet.com 2500 N. Partnership Boulevard Springfield, MO 65803
9.1 ZONE INFORMATION
This allows you to define the operation of each protection zone used in the system.
A description of each programming option follows:
9.2 ZONE NUMBER
Enter the number of the zone you intend to program. Press COMMAND to enter a
zone name. Refer to the Enter Alpha Characters section for information on entering
zone names.
9.3 ZONE NAME
Press the Select key and enter up to 16 characters for the zone name. A name must
be given to each zone in the system. This name can be displayed at the keypads
when the zone is bad or viewed in Display Events. The zone name is also sent to the
receiver as part of a zone event report.
A zone that is not part of the system must be marked *UNUSED*. To mark a zone
unused, delete the old name by pressing a top row Select key, then press the
COMMAND key. The programmer automatically programs the name as * UNUSED *.
If you selected ZONES? NO YES to clear the panel's memory during Initialization, the
zones will already be marked * UNUSED *. See the Initialization section.
9.4 ZONE TYPE
The Zone Type defines the panel's response to the zone being opened or shorted.
See the Zone Types Specifications chart.
When you assign a Zone Type to a zone, responses are made automatically for the
zone. There are 11 Zone Types to choose from including Blank. The functional
details of each response are described in Zone Types Specification.
To enter a new Zone Type, press a top row Select key. The display lists the four
Zone Types shown below.
Blank, Night, Day, or Exit. Press COMMAND to display additional zone types.
Fire, Panic, Emergency, or Supervisory. Press COMMAND to display additional zone
types.
Auxiliary 1, Auxiliary 2, Fire Verify, or Arming. Press the ARROW key to display the
previous zone types.
When the Zone Type you want to select is displayed, press the Select key beneath its
name. The chart in section 9.4A gives an outline of the Alarm Action for each Zone
Type.
If you select Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 as the Zone Type, the
zone must be assigned to an area.
If you select Fire, Panic, Emergency, or Supervisory as the Zone Type, these are 24-
hour zones that are always armed and no area assignment is needed. Press
COMMAND to continue.
Refer to the Appendix section in this guide for zone type descriptions.
ZONE INFORMATION
ZONE NO: –
ZONE INFORMATION
* UNUSED *
– – NT DY EX
F I PN EM SV
A1 A2 FV AR
ZONE TYPE: BLANK
Address
XRSuper
XR20
XR40
Zone # Zone # Zone #
Panel
1
-
6
1
-
10
1
-
10
1
7
-
10
11
-
14
11
-
14
2
21
-
24
21
-
24
21
-
24
3
31
-
34
31
-
34
31
-
34
4
41
-
44
41
-
44
41
-
44
5
N/A
N/A
51
-
54
6
N/A
N/A
61
-
64
7
N/A
N/A
71
-
74
8
N/A
N/A
81
-
84
Vedere la pagina 25