XTL/XTLC Programming Guide Digital Monitoring Products
29
ZONE INFORMATION
PLS (Pulse) - The output alternates one second on and one second off.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the on state and off state. Each button
press toggles the output state.
OFF (Off) - The output is turned off. If programmed, the output was turned on by some
other means such as another button press, a zone action, or a schedule.
Note: When the output is assigned to PN/PN2 or EM/EM2 button action and is turned
on, the output turns off when any area is disarmed.
When the output action is steady, pulse or toggle and the output is turned on, the
output remains on until:
— the output cutoff time expires
— the output is reset from the keypad menu
— toggled off
13.12 Alarm Action
The Alarm Action section allows you to change or conrm the default alarm
characteristics of a zone type.
If you selected the non-24-hour zone type Blank, Night, Day, Exit, Auxiliary 1, or
Auxiliary 2, the Alarm Action programing begins with Disarmed Open.
If you selected the 24-hour zone type Fire, Panic, Emergency, or Supervisory, the Alarm
Action programming begins with Armed Open.
13.13 Disarmed Open
Denes the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to dene:
• Message to Transmit
• Output/Favorite Number
• Output Action
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press the COMMAND key to continue.
13.13.1 Message To Transmit
You can send two report types to the receiver: Alarm and Trouble. These are represented
by the characters A and T. Press any Select key to display the zone report options.
ALARM - Selecting A allows an alarm report to be sent to the receiver and the wireless
siren output to activate according to zone type. See the Bell Action section. The zone
name appears in the panel’s alarmed zones status lists.
TROUBLE - Selecting T allows a trouble report to be sent to the receiver and the zone
name to appear in the panel’s alarmed zones status lists.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell output
still activates according to zone type and the zone name appears in the panel’s alarmed
zones status lists.
(dash) - When you select , reports are NOT sent to the receiver. The wireless siren
output does not activate and there is no display in the panel’s alarmed zones status list.
Only the programmed Output Number activates.
12.13.2 Output Number
You can specify any of the outputs/Favorites on the XTL/XTLC to be activated by a zone
condition. The output/Favorite can be activated regardless of the report to transmit or
whether or not the zone is programmed as local. An output activated by a non-24-hour
armed zone is turned off when the zone’s area is disarmed by a user.
To enter an Output Number, press any Select key followed by the output number
31-34, 41-44, or F01-F20. Press the COMMAND key.
OFF
ALARM ACTION . . .
DISARMED OPEN
MSG: TROUBLE
A T L -
OUTPUT NO: 0